Guangzhou Xiangbingyue Refrigeration Equipment Co., Ltd

Professional team , professional design and professional services !

Manufacturer from China
Active Member
8 Years
Home / Products / Air Cooled Condenser /

FNV Type Air Cooled Condenser 600 W For 8HP Refrigeration Condensing Unit

Contact Now
Guangzhou Xiangbingyue Refrigeration Equipment Co., Ltd
City:guangzhou
Province/State:guangdong
Country/Region:china
Contact Person:MrsLiz
Contact Now

FNV Type Air Cooled Condenser 600 W For 8HP Refrigeration Condensing Unit

Ask Latest Price
Video Channel
Brand Name :GaoXiang
Model Number :FNV Type
Certification :ISO , CE , CCC
Place of Origin :China
MOQ :1 Pcs
Price :EXW Price
Supply Ability :1000 Pcs / Day
Delivery Time :15 Work Days
Packaging Details :Standard Export Packing
Product Name :Heat Exchanger
Quantity Of Fan Motor :Customized
Power :600 W
Material :Copper Pipe & Aluminum Fin
Voltage :380 V
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

FNV Type Air Cooled Condenser For 8HP Refrigeration Condensing Unit

Condenser Description :

Air - cooled condenser is a kind of cooling equipment that is used in the cooling equipment of Foung . There are mainly four types of air - cooled condensers produced by our company : FNH type , FNV type , FNVB type , GP type , FNH type , side blowing type , FNV type , FNVB type , FNU type and GP type .

Products Feature :

● High - quality steel shell , the surface spray , corrosion - resistant , beautiful appearance ;
● The coil adopts the copper tube mis - arranging way , utilizes the mechanical expansion tube to make the copper tube and the fins closely combine , and the heat exchange effect is good ;
● products after 2.5MPa tightness test and system sewage treatment ;
● Applicable to R22 , R134a , R404a , R407c and other refrigerants ;
● FNV - type condenser with large windward side , good heat transfer , are equipped with low - noise motor ;
● High - performance heat exchange coil , clean and dry ;
● Adopt FZL series axial flow fan , air volume, low noise , low power consumption ;
● shell with high - quality galvanized sheet , spray treatment , corrosion - resistant durable ;
● Special - purpose products , please contact the company ' s sales department .

Technical Parameters :

Technical parameters of industrial condensers
Model

Heat -

exchange △t = 15kw

Heat-

exchange area

fan Diameter of inlet tube Diameter of outlet tube Dimensions Mounting dimensions
Quantity Diameter of fan Air volume Power Voltage
W m2 N φmm m3/h W V Φ mm Φ mm L B H D E
FNV - 26 / 72 25890 72 1 4D550 8487 600 380 22 16 950 900 880 870 700
FNV - 31 / 87 31320 87 1 4D600 10820 780 380 25 16 1100 1000 880 1020 700
FNV - 40 / 110 39800 110 2 4D500 2×6246 2×450 380 25 16 1400 900 880 1320 700
FNV - 47 / 130 46800 130 2 4D550 2×8487 2×600 380 28 19 1550 900 880 1470 700
FNV - 56 / 155 55800 155 2 4D500 2×8487 2×600 380 28 19 1600 1000 980 1520 800
FNV - 67 / 185 66700 185 2 4D600 2×12500 2×780 380 28 22 1700 1000 1080 1620 800
FNV - 76 / 210 75680 210 2 4D630 2×13000 2×800 380 32 22 1750 1000 1180 1670 800
FNV - 86 / 240 86420 240 2 φ700 2×15000 2×750 380 32 22 1900 1175 1260 1820 975
FNV - 108 / 300 10800 300 2 φ750 2×19000 2×1100 380 35 25 2250 1175 1260 2170 975
FNV - 115 / 320 11520 320 2 φ750 2×19000 2×1100 380 38 25 2350 1175 1260 2270 975
FNV - 130 / 360 129600 360 3 φ650 3×13200 3×550 380 42 28 2650 1175 1260 2570 975
FNV - 144 / 400 144000 400 3 φ700 3×15000 3×750 380 42 28 2950 1175 1260 2870 975
FNV - 173 / 480 172800 480 3 φ750 3×19000 3×1100 380 54 28 3400 1175 1260 3320 975

Note : four - pole external rotor fans shall be used for the heat - exchange area less than 210 ㎡ . And six - pole axial flow fans shall be used for the heat - exchange area more than 240 ㎡ .